Description
TOMC3-63 AC 4P 16A MCB provides indirect protection to the operator’s body under such condition that the exposed live parts should be connected to a proper earthing pole.It also provides protection against the fire danger caused by earth fault current due to function failure of over-current protection device.
1. MCB is for non-professional operation by those untrained, and no maintenance is required
2. Satisfying conditions and applications as mentioned above, MCB with “ON-OFF” indicating device is considered suitable for isolation function.
3. Particular devices such as surge protective devices, surge arrester, etc are recommended to install at upstream line to MCB as a precaution against potential surge voltage and current occurring at its power input side.
4. Appropriate tripping curve being chosen and properly installed, MCB trips and switches off its protected circuit in case of a fault, and thus provides protection against electric shock.
5. B, C, D tripping curve(see graphics 1):
1.Protection against both overload and short circuit
2.Contact position indication
3.Applicable to terminal and pin/fork type Busbar connection
4.Easy mounting onto 35mm DIN rail
Model Name | TOMC3-63/4/C16 |
Pole No: | 4 |
Rated voltage: | AC 110V 220V 400V |
Rated current(A): | 16 |
Tripping curve: | C |
Rated short-circuit capacity(lcn): | 3kA |
Rated frequency: | 50/60Hz |
Energy limiting class: | 3 |
Rated impulse withstand voltage: | 6.2kV |
Electro-mechanical endurance: | ≥ 6000 |
Contact position indication | |
Connection terminal: | Screw terminal / Pillar terminal with clamp |
Connection capacity: | Rigid conductor up to 25mm² |
Fastening torque: | 2.0Nm |
Installation: | On symmetrical DIN rail 35mm / Panel mounting |
Environment
Standards | IEC 60947-2, IEC 60898-1, EN60898-1 , AS/NES 60898.1 |
IP degree of protection | IP40 for modular enclosure conforming to IEC 60529 |
IP20 conforming to IEC 60529 | |
Operating altitude | 2000 m |
Ambient air temperature for operation | -35°C to +70°C |
Ambient air temperature for storage | -40°C to +85°C |
- + General
-
TOMC3-63 AC 4P 16A MCB provides indirect protection to the operator’s body under such condition that the exposed live parts should be connected to a proper earthing pole.It also provides protection against the fire danger caused by earth fault current due to function failure of over-current protection device.
1. MCB is for non-professional operation by those untrained, and no maintenance is required
2. Satisfying conditions and applications as mentioned above, MCB with “ON-OFF” indicating device is considered suitable for isolation function.
3. Particular devices such as surge protective devices, surge arrester, etc are recommended to install at upstream line to MCB as a precaution against potential surge voltage and current occurring at its power input side.
4. Appropriate tripping curve being chosen and properly installed, MCB trips and switches off its protected circuit in case of a fault, and thus provides protection against electric shock.
5. B, C, D tripping curve(see graphics 1): - + Feature
-
1.Protection against both overload and short circuit
2.Contact position indication
3.Applicable to terminal and pin/fork type Busbar connection
4.Easy mounting onto 35mm DIN rail
- + Technical Data
-
Model Name TOMC3-63/4/C16 Pole No: 4 Rated voltage: AC 110V 220V 400V Rated current(A): 16 Tripping curve: C Rated short-circuit capacity(lcn): 3kA Rated frequency: 50/60Hz Energy limiting class: 3 Rated impulse withstand voltage: 6.2kV Electro-mechanical endurance: ≥ 6000 Contact position indication Connection terminal: Screw terminal / Pillar terminal with clamp Connection capacity: Rigid conductor up to 25mm² Fastening torque: 2.0Nm Installation: On symmetrical DIN rail 35mm / Panel mounting Environment
Standards IEC 60947-2, IEC 60898-1, EN60898-1 , AS/NES 60898.1 IP degree of protection IP40 for modular enclosure conforming to IEC 60529 IP20 conforming to IEC 60529 Operating altitude 2000 m Ambient air temperature for operation -35°C to +70°C Ambient air temperature for storage -40°C to +85°C - + Dimension
-
- + Inquiry
-
Reviews